The Fireye Type 25SU5 Model Control, combined with remote Flame Scanners, comprises a repetitve self-checking flame safeguard system that confirms the flame presence and absence to provide reliable ignition and flame failure protection.

The Fireye 25SU5 Control enables the construction of integrated safety interlock systems for single and multiple burner fired apparatus including power, industrial process, and electric utility furnaces and boilers that fire gas, oil, pulverized coal or a combination of fuels on a continuous basis.

The 25SU5 Control may also be employed in the safety control circuits of supervised manual and semi-automatic burner management systems as the primary safety control. This flame safeguard system monitors flame to supervise burner and pilot performance throughout the entire burner load range.
25SU5 Controls Amplifier

Specs

Supply Voltage
120 VAC (102 min., 132 max.) 50/60 Hz
Maximum Flame Failure Response Time (FFRT)
Selectable 4 sec. or 1 sec. (Factory set at 4 sec.)
Nominal Shutter Operating Cycle
4.5 sec. open/0.5 sec. closed
Operating Temperature
+32 to +125 degrees fahrenheit (0 to +52 degrees Celsius)
Storage Temperature
Scanner and Control is -40 to +185 degrees Fahrenheit (-40 to +85 degrees Celsius)

Features

  • Easy Upgrade
  • Plug-In Convenience
  • Application Flexibility
  • Electrical and Mechanical Compatibility
  • Two Adapters are Available
Back To Top